Building a Raspberry Pi NUT Server for an Online Rack UPS (Proxmox, TrueNAS & Linux Clients)

I finally bought a proper UPS for the homelab: an Acconet 3kVA/2700W online double-conversion rack UPS (AC-UPS-O3000-R) from Miro. A UPS on its own only buys you time, though. What I actually wanted was for every machine in the rack to shut down cleanly when the battery runs low, and then come back up by itself when the power returns.

This post covers the whole process: rack-mounting the UPS, building a dedicated NUT (Network UPS Tools) server on a Raspberry Pi 3B, adding a web dashboard with PeaNUT, and connecting Proxmox, TrueNAS SCALE and a CachyOS desktop as clients. I also cover the problems I hit along the way, because this UPS needed a bit of coaxing.

What we’re building

  • The UPS connects to a Raspberry Pi 3B over USB. The Pi runs the NUT server and is the only machine that talks to the UPS directly.
  • The clients (Proxmox, TrueNAS and my CachyOS PC) watch the Pi over the network.
  • When the battery drops below 40% while on battery power, the Pi tells every client to shut down, then shuts itself down. The UPS then cuts its outputs.
  • When mains power returns, the UPS turns its outputs back on and everything boots by itself.
  • PeaNUT runs on the Pi as a web dashboard for monitoring.

Why a separate Pi instead of running NUT on the Proxmox host? The NUT server should be the last thing to go down. A Pi draws very little power, boots on its own the moment it gets power, and doesn’t depend on any VM or container being up.

Part 1: Rack-mounting the UPS

The rail kit (AC-UPS-RMKIT) confused me for a while, so here’s the short version. Each rail is an L-shaped shelf that adjusts in length. At every post, front and back, the stack from the outside in is:

3-hole flat strip → rack post → rail flange (threaded holes)

The screws go through the strip and through the square hole in the post, then thread into the rail flange. That clamps the post between the strip and the flange, so the rail is held firmly rather than hanging off the screws. The UPS then slides in and rests on the rails’ lips.

The supplied cage nuts are for the UPS’s own rack ears, which screw into the front posts wherever there isn’t a threaded rail hole behind them. The ears just stop the UPS from sliding out; the rails carry the weight. Use every screw hole, and get a second person to help lift the UPS in, because it weighs about 26 kg.

One more tip: the large “High Current Output” socket on the back is an IEC C19 (16 A) outlet. It’s on the same protected output as the other sockets and shares the same 2700 W total. You’ll need a lead with a C20 plug, such as a C20-to-multi-plug strip or a PDU, to use it.

Part 2: Flashing Raspberry Pi OS

I flashed the SD card from my CachyOS desktop using Raspberry Pi Imager. Install it with either of these:

sudo pacman -S rpi-imager
# or, as a Flatpak:
flatpak install flathub org.raspberrypi.rpi-imager

The app menu lists it as “Raspberry Pi Imager”, so search for “Raspberry” rather than “rpi”. On Windows, download the installer from raspberrypi.com/software instead.

Pick Raspberry Pi 3 as the device.

For the OS, go to Raspberry Pi OS (other) and choose Raspberry Pi OS Lite (64-bit). You don’t need a desktop on a headless NUT server.

Select your SD card, checking its size so you know it’s the right one. Leave Exclude system drives ticked so you can’t pick the wrong disk.

OS customisation

Imager lets you preconfigure everything, so the Pi is reachable over SSH on first boot without ever connecting a screen. I used these settings:

  • Hostname: nut
  • Localisation: your time zone and keyboard layout
  • User: your username and password
  • Wi-Fi: skipped, because this box is on Ethernet
  • SSH: enabled with password authentication. Public-key authentication is more secure if you prefer it, but a password is fine on a LAN-only box.

On Linux, Imager asks for your password through a polkit prompt before it writes to the card. Approve it, wait for the write to finish, and remove the card.

Part 3: First boot and updates

Put the card in the Pi, plug the Pi’s power supply into a UPS output, and connect Ethernet and the UPS’s USB cable. Find the Pi’s IP in your router’s DHCP list and set a DHCP reservation for it there, so the address never changes.

ssh <user>@<pi-ip>

Update everything and turn on automatic security updates:

sudo apt update && sudo apt full-upgrade -y
sudo apt install -y unattended-upgrades
sudo dpkg-reconfigure -plow unattended-upgrades # choose Yes
sudo reboot

Part 4: Installing NUT and detecting the UPS

sudo apt install -y nut nut-client nut-server
lsusb
sudo nut-scanner -U

The UPS appears as 0001:0000 Fry's Electronics MEC0003. That’s a generic USB chip used in many OEM online UPSes. nut-scanner suggests the nutdrv_qx driver, which turns out to be correct. The “Cannot load SNMP/XML/AVAHI/IPMI library” warnings are harmless; they only disable scan types you don’t need.

Gotcha #1: USB permissions

The first driver start failed with this error:

libusb1: Could not open any HID devices: insufficient permissions on everything

The NUT driver runs as the nut user, and NUT’s bundled udev rules don’t include this chip’s 0001:0000 ID. Adding a rule fixes it:

sudo nano /etc/udev/rules.d/90-nut-ups.rules
SUBSYSTEM=="usb", ATTR{idVendor}=="0001", ATTR{idProduct}=="0000", MODE="0664", GROUP="nut"
sudo udevadm control --reload-rules
sudo udevadm trigger
ls -l /dev/bus/usb/001/ # the UPS device should now be group "nut"

After that, sudo upsdrvctl start acconet reported Using protocol: Megatec 0.07, so the driver was talking to the UPS.

Gotcha #2: Battery charge stuck at 0%

With the driver running, upsc acconet showed battery.voltage: 2.26 and battery.charge: 0. The UPS reports per-cell voltage (2.26 V × 36 cells ≈ 81 V for the 6 × 12 V battery bank), but the driver was comparing it against a whole-pack range of 62.4–78 V.

NUT has a battery_voltage_reports_one_pack flag for this, but on NUT 2.8.1 with this UPS it was accepted and then had no effect. The fix that worked was to define the battery range per cell instead: 2.26 V is full (the float voltage the UPS sits at) and 1.75 V is empty (the usual lead-acid cut-off).

Part 5: The complete NUT server config

/etc/nut/ups.conf

[acconet]
driver = nutdrv_qx
port = auto
vendorid = 0001
productid = 0000
desc = "Acconet 3kVA"

# battery reports per-cell voltage
default.battery.voltage.high = 2.26
default.battery.voltage.low = 1.75

# runtime estimate
runtimecal = 240,100,720,50
chargetime = 14400
idleload = 5

# shut everything down at 40% on battery
ignorelb
override.battery.charge.low = 40

# after the Pi halts, cut UPS output in 600 s; restore 60 s after mains returns
offdelay = 600
ondelay = 60

What each section does:

  • Runtime estimate: this UPS doesn’t report runtime, so runtimecal gives NUT a rough calibration: about 4 minutes at 100% load and 12 minutes at 50%. It’s a ballpark figure for 6 × 9 Ah batteries; tune it after a real outage. chargetime is 4 hours to full, per the datasheet.
  • Shutdown threshold: ignorelb with override.battery.charge.low = 40 means the low-battery signal triggers at 40%, not whenever the UPS decides. The charge percentage is estimated from voltage, so I kept a generous buffer.
  • Power cycling: offdelay and ondelay are both in seconds for this driver. The reason for them is explained in Part 8.

/etc/nut/nut.conf

MODE=netserver

/etc/nut/upsd.conf

LISTEN 0.0.0.0 3493

/etc/nut/upsd.users

[admin]
password = <strong-password-1>
upsmon primary
actions = SET
instcmds = ALL

[monuser]
password = <strong-password-2>
upsmon secondary

[peanut]
password = <strong-password-3>
upsmon secondary
instcmds = beeper.toggle
instcmds = test.battery.start.quick
instcmds = test.battery.start
instcmds = test.battery.stop
instcmds = shutdown.stop

Each account has a different job:

  • admin is used by the Pi’s own monitor.
  • monuser is the account every client logs in with.
  • peanut is a deliberately limited account for the dashboard. It can run battery tests and toggle the beeper, but it can’t run load.off or shutdown.stayoff, which cut power to the whole rack instantly. Those are not buttons you want one misclick away. It still needs upsmon secondary, though: without it, PeaNUT’s credential check fails with “Invalid credentials” even when the password is correct. That line only allows it to log in as a monitor; it grants no extra commands.

Tip: use letters and numbers only in these passwords. TrueNAS rejected my login until I removed the special characters.

/etc/nut/upsmon.conf

MONITOR acconet@localhost 1 admin <strong-password-1> primary

Start and verify

sudo systemctl enable --now nut-driver-enumerator nut-server nut-monitor
sudo systemctl restart nut-driver@acconet nut-server nut-monitor
upsc acconet

You should now see ups.status: OL, battery.charge: 100, and real input and output voltages. Note that restarting nut-driver-enumerator does not restart the driver itself. After editing ups.conf, always run sudo systemctl restart nut-driver@acconet.

Part 6: A web dashboard with PeaNUT

NUT has no web UI of its own. PeaNUT fills that gap well, and it has ARM64 images, so it runs fine on the Pi 3B. Running it on the Pi also means the dashboard stays up while everything else shuts down.

curl -fsSL https://get.docker.com | sh
sudo usermod -aG docker $USER # log out and back in afterwards
sudo mkdir -p /opt/stacks/peanut

/opt/stacks/peanut/compose.yaml:

services:
peanut:
image: brandawg93/peanut:latest
container_name: peanut
restart: unless-stopped
network_mode: host
volumes:
- ./config:/config
environment:
- NUT_HOST=127.0.0.1
- NUT_PORT=3493
- WEB_PORT=8080
logging:
options:
max-size: "5m"
max-file: "2"
cd /opt/stacks/peanut
sudo docker compose up -d

Because the folder was created with sudo, the config directory is owned by root, but PeaNUT runs as a normal user inside the container. Its logs then show config directory /config still not writable, and any settings you change in the UI are lost on restart. Give the folder to the container’s user:

sudo chown -R $(sudo docker exec peanut id -u):$(sudo docker exec peanut id -g) config
sudo docker compose restart

Two settings in that file matter. network_mode: host lets the container reach NUT on 127.0.0.1 without extra networking setup. The log limits keep Docker from wearing out the SD card. Browse to http://<pi-ip>:8080, then in Settings → Manage Servers give the server a name and enter the peanut username and password. The status dot should turn green.

If it stays red, check sudo docker logs peanut --tail 30. A quick way to separate a connection problem from a login problem is to clear the username and password and apply again: green without credentials means NUT is reachable and only the login is failing. And no, 127.0.0.1 isn’t the issue here. With network_mode: host, it points at the Pi, not the container.

If the runtime card shows N/A after you add runtimecal, run upsc acconet battery.runtime on the Pi first. If that returns a number, PeaNUT just needs a hard refresh.

Part 7: Connecting the clients

Every client gets the same minimal config. The shutdown policy lives on the Pi, so there’s nothing to tune per machine.

Proxmox (Debian)

apt install -y nut-client

/etc/nut/nut.conf:

MODE=netclient

/etc/nut/upsmon.conf:

MONITOR acconet@<pi-ip> 1 monuser <strong-password-2> secondary
systemctl enable --now nut-monitor
systemctl restart nut-monitor
journalctl -u nut-monitor -n 10 --no-pager

Make sure you replace the <pi-ip> placeholder with the real address. If you don’t, the log fills up with connect failed: No such host.

TrueNAS SCALE (GUI)

Go to System → Services → UPS → Edit and set:

  • Identifier: acconet
  • UPS Mode: Slave
  • Remote Hostname: <pi-ip>, Port: 3493
  • Monitor User / Password: monuser and its password
  • Shutdown Mode: UPS reaches low battery
  • Power Off UPS: unticked, because the Pi handles that

Turn the service on and tick Start Automatically. If it doesn’t connect, check from System → Shell:

upsc acconet@<pi-ip> ups.status
sudo journalctl -u nut-monitor -n 20 --no-pager

An ERR ACCESS-DENIED error means TrueNAS can reach the Pi but the login is wrong. In my case, that was special characters in the password.

CachyOS / Arch

sudo pacman -S nut
# /etc/nut/nut.conf -> MODE=netclient
# /etc/nut/upsmon.conf -> same MONITOR ... secondary line as above
sudo systemctl enable --now nut-monitor

Check every client is connected

On the Pi, this lists every connected monitor:

upsc -c acconet

Part 8: How the shutdown and power-on sequence works

The Pi doesn’t send shutdown commands to the clients. It raises a status flag. When the UPS is on battery and below 40%, the status becomes OB LB and the Pi adds FSD (forced shutdown). Each client’s upsmon polls the Pi, sees the flag, and runs its own local SHUTDOWNCMD, which by default is a normal OS shutdown. On Proxmox, that shutdown stops VMs and containers properly before powering off.

The full sequence:

  1. The UPS goes on battery and the charge drops below 40%.
  2. The Pi raises FSD, and every client starts a clean shutdown.
  3. The Pi waits briefly for the clients to disconnect, then shuts itself down.
  4. The UPS cuts its outputs after offdelay (600 seconds).
  5. When mains returns, the outputs come back after ondelay (60 seconds), and everything boots.

Why the UPS needs to cut power at the end

Here’s the trap. If mains comes back after everything has shut down but before the battery runs flat, the UPS output never actually turned off. Your servers would sit powered off until someone pressed their buttons. Cutting the output and then restoring it makes the machines see a real power cycle.

For that to work, set this in the BIOS of every server:

  • Find the option called something like Restore on AC Power Loss, After Power Failure or AC Power Recovery.
  • Set it to Power On.
  • Don’t choose “Last State”. After a clean shutdown, the last state was off, so the machine stays off.

The Pi needs nothing; it always boots when it gets power.

Sizing offdelay for a busy Proxmox host

The Pi doesn’t wait for the clients to finish shutting down. So the time Proxmox actually gets is roughly 20 seconds, plus the Pi’s own halt time, plus offdelay. Measure your host’s real shutdown time from its previous boot’s journal:

journalctl -b -1 -o short-precise | grep -E "Stopping|Reached target.*Power-Off" | head -n 3
journalctl -b -1 -o short-precise | tail -n 3

My host took 6 minutes 35 seconds, which is a sign that a guest was hitting Proxmox’s 180-second shutdown timeout. So I set offdelay = 600, the maximum this UPS accepts. To speed things up:

  • Enable the QEMU guest agent on your VMs.
  • Tune each guest’s Start/Shutdown order and timeout in the Proxmox GUI.

Part 9: Testing

Quick test: pull the UPS’s wall plug. upsc acconet ups.status should change from OL to OB, and every client should log the event. Plug it back in.

Full test: do this when a complete shutdown is acceptable. This triggers the whole sequence on purpose:

sudo upsmon -c fsd

Everything should shut down, the UPS should cut power about 10 minutes later, and then everything should boot back up. Afterwards, check that all the clients reconnected with upsc -c acconet.

Troubleshooting cheat sheet

SymptomCauseFix
insufficient permissions on everythingNo udev rule for 0001:0000Add the udev rule from Part 4
battery.charge: 0 with battery.voltage: 2.26The UPS reports per-cell voltageSet default.battery.voltage.high/low to 2.26 / 1.75
ups.conf changes not applyingOnly the enumerator was restartedsudo systemctl restart nut-driver@acconet
Battery runtime shows N/AThe UPS doesn’t report runtimeAdd runtimecal, then refresh PeaNUT
PeaNUT: Invalid credentialsThe peanut user can’t log in as a monitorAdd upsmon secondary to [peanut], restart nut-server
PeaNUT: /config still not writableConfig folder owned by rootchown it to the container’s user
connect failed: No such hostPlaceholder left in MONITORUse the Pi’s real IP address
ERR ACCESS-DENIEDWrong or mangled passwordUse a password with letters and numbers only
Servers stay off after an outageBIOS set to Off or Last StateSet “Restore on AC Power Loss” to Power On

Wrapping up

For the cost of a Raspberry Pi 3B I had lying around, the rack now handles outages without me: a clean shutdown at 40%, a proper power cycle, and an automatic boot when power returns, with a dashboard to keep an eye on it all. If you have a similar OEM online UPS that shows up as MEC0003, the udev rule and the per-cell battery voltage fix are the two pieces you’ll most likely need.

Gemini_Generated_Image_itfa1qitfa1qitfa

Retro Gaming From the NAS: RGSX on TrueNAS, Batocera, and Sunshine Streaming on KDE Wayland

I wanted a proper retro gaming setup for the lounge: download games from a nice web interface, store everything on the NAS, play it all on a Batocera box under the TV, keep save files safe and backed up, and, as a bonus, stream my modern PC games from my desktop to the same TV. After an evening of tinkering it all works, and it works well. This post walks through the whole build, including every wall I hit along the way, because the gotchas are where the real value is.

The end result

  • RGSX runs as a custom app on TrueNAS SCALE and downloads ROMs and BIOS files straight into NAS datasets.
  • Batocera on a small lounge PC mounts the ROMs, BIOS and saves folders from the NAS over SMB. Nothing game-related lives on the lounge PC itself.
  • Saves are snapshotted and backed up off-site along with the rest of the NAS.
  • Sunshine on my CachyOS desktop (KDE Plasma on Wayland) streams Steam Big Picture to Moonlight on the Batocera box, with my ultrawide monitor switching to a 16:9 resolution automatically while streaming.

The lounge PC and the NAS sit on different VLANs, which adds a firewall step or two. I’ve included those too.

Part 1: RGSX on TrueNAS SCALE

RGSX is a ROM download manager built for Batocera, Knulli and RetroBat. Most people run it on the console itself, but the repo also ships a Docker setup that runs it headless with a web UI. That’s perfect for a NAS: downloads land directly on the storage, with no copying step.

Datasets

I created a parent dataset called Retro with three children, plus a config dataset for the app:

tank/Retro/ROMs      # games, one folder per platform
tank/Retro/BIOS      # BIOS files
tank/Retro/Saves     # Batocera save files and states
tank/Apps-Config/rgsx   # RGSX settings, history, API keys

I shared Retro over SMB and gave both the TrueNAS apps user (UID/GID 568) and my SMB user Full Control on the ROMs and BIOS datasets. Running the container as apps saved me from fighting parent-folder traverse permissions, because that user already owns the app config datasets.

The app YAML

TrueNAS SCALE 24.10 and later can run any Docker Compose file under Apps → Discover Apps → ⋮ → Install via YAML. RGSX has no published image, so the compose file builds it from the GitHub repo:

services:
  rgsx:
    build:
      context: https://github.com/RetroGameSets/RGSX.git#main
      dockerfile: docker/Dockerfile
    image: rgsx:local
    container_name: rgsx
    restart: unless-stopped
    ports:
      - "30500:5000"
    environment:
      - PUID=568
      - PGID=568
    volumes:
      - /mnt/tank/Apps-Config/rgsx:/config
      - /mnt/tank/Retro/ROMs:/data/roms
      - /mnt/tank/Retro/BIOS:/data/bios

The web UI is then at http://NAS-IP:30500. On first load, click Update games list and refresh. Until you do that, it shows “No platforms found”, which looks alarming but just means the lists haven’t been fetched yet.

Gotchas I hit

The app showed “Deploying”, then “Stopped”, with no containers and no logs. If the Workloads panel says “No containers are available”, the container was never created, which means the build failed. Check the job in Task Manager (the clipboard icon at the top right) for the reason. If your TrueNAS version won’t build from a build: block, build the image on another machine, push it to a registry (Docker Hub, or your own Forgejo/Gitea registry over HTTPS), and swap build: for image: youruser/rgsx:latest.

mkdir: cannot create directory '/config': Permission denied. The container was running as a UID that couldn’t get into the config dataset. Running as apps (568) fixed it.

BIOS downloads vanished. RGSX doesn’t put BIOS files in a ROMs platform folder. It extracts them into the data root, which is /data in Docker. If you only mount /data/roms, BIOS files end up inside the container and are lost on the next update. Mounting a dataset at /data/bios catches them, because the BIOS pack extracts into a bios/ folder.

Downloads failed at 95–100% with [Errno 1] Operation not permitted. This was the sneaky one. The file downloads fine, then RGSX runs chmod 644 on it, and that chmod is refused. Datasets created with TrueNAS’s SMB preset use the ZFS ACL mode Restricted, which rejects every chmod call, no matter how much access you grant in the ACL. The fix is to set the dataset’s ACL Mode to Discard under Edit → Advanced Options. Chmod calls then succeed silently without touching your ACL. Don’t use Passthrough: chmod 644 would rewrite the ACL and strip write access.

# If the ACL Mode dropdown is locked, one-off from System → Shell:
zfs set aclmode=discard tank/Retro/ROMs
zfs set aclmode=discard tank/Retro/BIOS

You’ll also see warnings about a missing rom_extensions.json and “no system found for /data/roms/…” in the logs. These are harmless in Docker: RGSX normally reads Batocera’s system list, which doesn’t exist inside the container.

Part 2: Batocera reading everything from the NAS

Batocera can mount individual userdata folders from network shares. RGSX already uses Batocera’s folder names (psx, snes, megadrive and so on), so the ROMs folder drops straight in.

Getting in over SSH

The user is root. Newer Batocera versions may not use the old default password. The current one is shown under Main Menu → System Settings → Security.

batocera-boot.conf

mount -o remount,rw /boot
cp /boot/batocera-boot.conf /boot/batocera-boot.conf.bak
nano /boot/batocera-boot.conf

Change sharedevice=INTERNAL to sharedevice=NETWORK, then add:

sharenetwork_smb1=ROMS@NAS-IP:Retro/ROMs:username=SMBUSER,password=SMBPASS,vers=3.0
sharenetwork_smb2=BIOS@NAS-IP:Retro/BIOS:username=SMBUSER,password=SMBPASS,vers=3.0
sharenetwork_smb3=SAVES@NAS-IP:Retro/Saves:username=SMBUSER,password=SMBPASS,vers=3.0
sharewait=30

The ROMS@, BIOS@ and SAVES@ prefixes mount only those folders, so the rest of Batocera’s config stays local. Use the NAS’s IP rather than its hostname, especially across VLANs, and avoid commas in the password because they break the line. After a reboot, check the mounts:

mount | grep cifs

You should see /userdata/roms, /userdata/bios and /userdata/saves. System Settings → Storage Device showing blank is normal with this setup.

Reading the mount errors

If nothing mounts, grep -i cifs /var/log/messages tells you why:

  • return code = -101 (network unreachable) in the first few seconds of boot is harmless. The network just isn’t up yet, and sharewait covers it.
  • return code = -13 (permission denied) means the login was rejected. In my case the user had dataset permissions but wasn’t on the SMB share ACL, which TrueNAS checks first. Test the login from another machine with smbclient //NAS-IP/Retro -U SMBUSER -m SMB3 -c 'ls' to separate a credentials problem from a permissions problem.

Crossing VLANs on a MikroTik

Batocera only needs TCP 445 to the NAS. One forward rule is enough, because the standard “accept established, related” rule handles the replies. In Winbox: IP → Firewall → Filter Rules → +, chain forward, source the Batocera box (give it a static DHCP lease first), destination the NAS, protocol tcp, dst-port 445, action accept. Then drag it above any inter-VLAN drop rules. To test it from Batocera:

timeout 3 bash -c '</dev/tcp/NAS-IP/445' && echo "SMB reachable" || echo "blocked"

Part 3: Multi-disc games

Batocera groups multi-disc games using an .m3u playlist. Per the Batocera wiki, each game can live in its own normal folder with the playlist inside:

psx/
└── Metal Gear Solid/
    ├── Metal Gear Solid.m3u
    ├── Metal Gear Solid (USA) (Disc 1) (Rev 1).chd
    └── Metal Gear Solid (USA) (Disc 2) (Rev 1).chd

The .m3u holds one bare filename per line. Use no ./ prefix: Batocera only hides the individual disc entries when the playlist uses plain filenames in the same folder. The easiest way to avoid copy-paste whitespace problems is to write the file over SSH:

printf '%s\n' "Metal Gear Solid (USA) (Disc 1) (Rev 1).chd" "Metal Gear Solid (USA) (Disc 2) (Rev 1).chd" \
  > "/userdata/roms/psx/Metal Gear Solid/Metal Gear Solid.m3u"
cat -A "/userdata/roms/psx/Metal Gear Solid/Metal Gear Solid.m3u"

That cat -A check is there because of my own mistake: my first playlist had three leading spaces on each line. The game showed a black screen and dropped straight back to the menu. /userdata/system/logs/es_launch_stderr.log gave it away. The emulator was looking for a file literally named " Metal Gear Solid…". Each line in cat -A output should start with the filename and end in $, with no ^M (Windows line endings) and no leading spaces.

Swapping discs in-game: Hotkey + B opens the RetroArch menu, then go to Disc Control.

Part 4: Scraping box art

TheGamesDB matches by name only, so oddly named files miss. ScreenScraper matches most ROMs by checksum, and a free account is plenty for a home library. Two tips:

  • Log in with your ScreenScraper username, not your email. The website accepts either, but the API only accepts the username, and the error you get (“Erreur de login : Vérifier les identifiants utilisateurs !”) is in French.
  • Long passwords are painful to type on an on-screen keyboard. Stop EmulationStation and paste them into the settings file over SSH instead:
/etc/init.d/S31emulationstation stop
nano /userdata/system/configs/emulationstation/es_settings.cfg
#   <string name="ScreenScraperUser" value="your_username" />
#   <string name="ScreenScraperPass" value="your_password" />
/etc/init.d/S31emulationstation start

Some sources also give files a prefix like Nintendo - Nintendo Entertainment System_Game Name.zip. Renaming them to just the game name helps the fallback name search and looks much cleaner in the list.

Part 5: Streaming PC games with Sunshine on KDE Wayland

I’d tried this before, given up, and blamed Wayland. It turns out the tooling has caught up. Sunshine v2026.516 added native KWin screencast capture, and Sunshine’s own docs now recommend kwin capture with vulkan encoding for KDE Plasma. No KMS hacks are needed.

Install and verify

First, confirm your GPU can hardware-encode:

sudo pacman -S --needed libva-utils
vainfo | grep -i enc     # look for VAEntrypointEncSlice on H264 / HEVC

CachyOS’s own repo already carried a version newer than 2026.516, so sudo pacman -S sunshine was enough. On plain Arch, LizardByte’s official pacman repo is the alternative. Then check that the package includes the KWin permission file. That .desktop entry is what authorises Sunshine to use KDE’s restricted screencast protocol:

pacman -Qi sunshine | grep Version
ls /usr/share/applications | grep -i sunshine   # needs ...Sunshine.kwin.desktop
getcap $(readlink -f /usr/bin/sunshine)         # cap_sys_admin,cap_sys_nice (KMS fallback)

sudo usermod -aG input $USER    # virtual gamepads; reboot afterwards
systemctl --user enable --now app-dev.lizardbyte.app.Sunshine

In the web UI at https://localhost:47990, the capture and encoder options are on the Advanced tab (not Audio/Video): set Force a Specific Capture Method to KWin Screencast and Force a Specific Encoder to Vulkan. A healthy log shows Found H.264 encoder: h264_vulkan [vulkan] and the same for HEVC and AV1.

If KWin capture ever misbehaves, Sunshine documents two fallbacks: portal capture, pre-approved with flatpak permission-set kde-authorized remote-desktop dev.lizardbyte.app.Sunshine yes (this works for non-Flatpak installs too), or kms, which the package’s capabilities already allow.

An ultrawide host and a 16:9 TV

Streaming a 3440×1440 desktop to a 16:9 TV gives you a short, letterboxed picture. Sunshine’s Command Preparations fix that by switching the monitor’s mode for the duration of the stream using kscreen-doctor. First find your output name and modes:

kscreen-doctor -o
# Output name is right after "Output: N", e.g. DP-2
# The current mode is marked with *, e.g. 3440x1440@165

Test both commands by hand, because a failing Do command blocks the stream from launching. Then add them under Configuration → General → Command Preparations:

StepCommand
Dokscreen-doctor output.DP-2.mode.1920x1080@60
Undokscreen-doctor output.DP-2.mode.3440x1440@165

With two monitors, also set Audio/Video → Display Id to the ultrawide’s output so Sunshine captures the right screen. Games open on the primary display, so streaming the primary one avoids “the game opened on the other monitor” surprises.

Firewall

Moonlight needs these ports from the Batocera box to the PC:

ProtocolPortsPurpose
TCP47984, 47989, 48010Pairing, HTTPS, RTSP
UDP47998–48000Video, control, audio

On the MikroTik, that’s two more forward rules alongside the SMB one. On the PC, my previous attempt had left ufw rules in place, including 47990/tcp (the Sunshine admin page) open to anyone. You only ever use that page via localhost, so close it:

sudo ufw delete allow 47990/tcp

Moonlight on Batocera

On Batocera v43, Moonlight is the full Moonlight Qt client. Enable it with:

mkdir -p /userdata/roms/moonlight
touch /userdata/roms/moonlight/Moonlight.moonlight

Update gamelists and launch it. Across VLANs, the PC won’t be auto-discovered (mDNS doesn’t cross subnets), so use Add PC manually with its IP, then enter the PIN in Sunshine’s PIN tab. Streaming 1080p60 HEVC at around 20 Mbps works well. The lounge PC’s old Intel iGPU decodes HEVC in hardware, but not AV1, so avoid AV1 on older clients.

Steam Big Picture

This is Sunshine’s documented Linux app setup. Steam restarts itself on launch, so it has to be a detached command:

FieldValue
Application NameSteam Big Picture
Detached Commandssetsid steam steam://open/bigpicture
Command Preparations → Undosetsid steam steam://close/bigpicture
Imagesteam.png

Disconnect is not quit

This one caught me out. In Moonlight, L1 + R1 + Start + Select disconnects but leaves the app running on the host, so the Undo commands never run and the monitor stays at 1080p. When I then picked a different app, Moonlight started crashing every time I selected the PC. The fixes:

  • Turn on “Quit app on host PC after ending stream” in Moonlight’s settings. The controller combo then ends the session properly, and the resolution switches back.
  • If a session gets stuck, use Troubleshooting → Force Close in Sunshine’s web UI (this runs the Undo too), then Restart.
  • As a last resort, run the Undo kscreen-doctor command by hand.

Odds and ends

  • Protect the saves. Retro/Saves is now the only copy of every save file. I snapshot the whole Retro dataset daily and include Saves in my off-site cloud sync. ROMs can be re-downloaded; saves can’t.
  • Back up batocera-boot.conf to the NAS so a reinstall takes two minutes: cp /boot/batocera-boot.conf /userdata/saves/.
  • PS1 upscaling on weak hardware: switching to SwanStation’s hardware renderer on an Intel HD 530 gave me audio with a black screen. PCSX-ReARMed (the default) with its own enhanced-resolution option is the safer route on an old iGPU.
  • Restart time: RGSX’s Docker entrypoint runs a recursive ownership change over /data on every start. That’s harmless with a small library, but expect slower app restarts as it grows.

Wrapping up

The finished workflow is lovely: pick a game in RGSX’s web UI from my phone, it lands on the NAS, I hit “Update gamelists” on the TV, and it’s there with box art. Saves follow the games, and the NAS backs them up. When I want something modern, Steam Big Picture is one menu away. Most of the friction along the way came from permissions (ZFS ACL modes, share ACLs, parent traverse) and from small details like whitespace in a playlist, so if you build something similar, those are the places to look first.

References

Gemini_Generated_Image_529gir529gir529g

Storj’s $50 Minimum Fee Killed It for Me — Here’s What I Switched To

Migrating from Storj.io to Z1 Storage on TrueNAS SCALE

Here’s the updated post with that corrected throughout:


Ditching Storj: How I Moved My TrueNAS Backups to a Local SA Alternative for a Fraction of the Price

If you’ve been using Storj for cloud backups, you’ve probably received the email by now. From 1 July 2026, Storj is introducing a $50 per month minimum fee — regardless of how much storage you actually use. For homelab users and small self-hosters backing up less than 7TB, that’s a significant and unwelcome change.

This post covers how I migrated my TrueNAS SCALE backup setup away from Storj to Z1 Storage, a South African S3-compatible object storage provider — and why it ended up being a better fit than the more commonly recommended Backblaze B2.


What Changed with Storj

Storj’s new pricing structure, effective 1 July 2026, introduces two tiers (Standard at $7/TB and Advanced at $10/TB) and eliminates the old segment fees. On paper that sounds reasonable — but the $50/month minimum is the dealbreaker for most homelab users. If your backup footprint is under 7TB, you’re paying more than your actual usage warrants, with no credit for the difference.

Accounts that don’t opt in before the deadline will be frozen and data deleted within 45 days, so this isn’t something you can ignore.


Why Not Backblaze B2?

Backblaze B2 is the most commonly recommended Storj alternative — no minimum fee, $6/TB/month, and free egress via the Cloudflare Bandwidth Alliance. For many users it’s the right choice.

However, Backblaze only operates datacenters in the US and EU. If you’re based in South Africa, you’re routing every backup upload across an international link. For small incremental backups that’s probably fine, but when a local alternative exists at a similar price point, it’s worth considering.


Enter Z1 Storage

Z1 Storage is a South African S3-compatible object storage provider with datacenters in Johannesburg and Cape Town. It’s priced at R0.30/GB per month (roughly R300/TB), includes free ingress, and egress equal to your stored data per month at no charge. There’s no minimum monthly fee.

It’s fully S3-compatible — meaning rclone, TrueNAS Cloud Sync tasks, BackWPup, and virtually any other S3-aware tool works with it out of the box. For a sub-1TB backup footprint you’re looking at well under R200/month, billed in Rands with no USD/ZAR exchange rate exposure.


The Migration: TrueNAS SCALE

My setup consisted of several TrueCloud Backup Tasks (Storj’s Restic-based integration) and one Cloud Sync task. The key thing to understand is that TrueCloud Backup Tasks are Storj-specific — you can’t simply swap the credential to Z1 Storage. They need to be replaced with standard Cloud Sync tasks.

Step 1: Add Z1 as a Cloud Credential

Go to Credentials → Backup Credentials → Cloud Credentials → Add and fill in:

  • Provider: Amazon S3
  • Endpoint URL: https://s3.z1storage.com
  • Access Key ID: your Z1 Storage access key
  • Secret Access Key: your Z1 Storage secret key
  • Region: leave blank, check Disable Endpoint Region

Click Verify Credential before saving. The endpoint needs the full https:// prefix — s3.z1storage.com alone or with :443 appended will throw a validation error.

Step 2: Disable Old TrueCloud Tasks

Toggle off all existing TrueCloud Backup Tasks in Data Protection. Don’t delete them yet — keep them until Z1 Storage is confirmed working.

Step 3: Create Your Buckets

I created a dedicated bucket in Z1 Storage for each dataset I was backing up, rather than using subfolders inside a single bucket. This keeps things clean and makes it easy to see per-dataset usage at a glance in the Z1 Storage console. For example:

  • personal-storage → one bucket
  • immich-library → one bucket
  • audiobookshelf → one bucket
  • Each WordPress site → its own bucket

It’s a personal preference — one bucket with subfolders works just as well technically — but separate buckets make storage reporting and cleanup much more straightforward.

Step 4: Create Cloud Sync Tasks

For each dataset, create a new Cloud Sync Task under Data Protection with:

  • Direction: PUSH
  • Transfer Mode: SYNC
  • Credential: Z1 Storage
  • Bucket: the dedicated bucket for that dataset
  • Folder: / (root of the bucket)

Under Advanced Options, set Transfers to High Bandwidth (16) and ensure Use –fast-list is ticked. This significantly improves throughput on datasets with large numbers of small files — particularly relevant for photo libraries.

Step 5: Run and Verify

Run each task manually first and verify in the Z1 Storage File Explorer that files are landing in the correct buckets. The initial upload will take longer than subsequent runs — after that, only new or changed files are transferred.

One gotcha: Z1 Storage occasionally returns a 502 Bad Gateway during the final cleanup phase of a sync, even after all files have transferred successfully. If this happens, simply rerun the task — it completes the verification pass quickly and exits cleanly.


WordPress Backups with BackWPup

For WordPress sites, BackWPup (free) supports S3-compatible storage natively. I created a dedicated Z1 Storage bucket per WordPress site, keeping each site’s backups completely isolated. In your job’s To: S3 Service tab, configure it as follows:

  • S3 Service: Custom
  • S3 Server URL: https://s3.z1storage.com
  • Region: us-east-1 (dummy value — Z1 Storage doesn’t require it but the field can’t be left blank)
  • Signature: v4
  • Access Key / Secret Key: your Z1 Storage credentials
  • S3 Bucket: the dedicated bucket for that WordPress site
  • Max backups to retain: 14–15

Hit Save & Test Connection and you’re done.


Cost Comparison

ProviderPriceMinimum FeeLocation
Storj$7/TB$50/monthGlobal
Backblaze B2$6/TBNoneUS / EU
Z1 StorageR0.30/GBNoneSouth Africa

For a ~500GB backup footprint, Z1 Storage works out to approximately R150/month — no surprises, no minimums, billed locally.


Final Thoughts

The Storj pricing change is a real problem for anyone running sub-7TB homelab backups. If you’re in South Africa, Z1 Storage is worth serious consideration — local latency, Rand-denominated billing, full S3 compatibility, and no minimum fee make it a compelling fit for exactly this use case.

The migration from TrueCloud to Cloud Sync tasks takes an hour or two, and the initial upload is the only slow part. Once that’s done, incremental daily backups are fast and cheap.

Gemini_Generated_Image_qpefjnqpefjnqpef

3-2-1 and Then Some: How I Back Up My Entire Home Lab

A comprehensive breakdown of my homelab backup architecture, built around the “3-2-1” principle. The strategy utilizes TrueNAS as the central hub, employing ZFS snapshots for immediate disaster recovery, Rsync to a secondary PC for local hardware redundancy, and Proxmox Backup Server for managing VM/LXC backups. Finally, all critical datasets and backups are automatically synced offsite to Storj, ensuring the entire network is well protected against failure

Gemini_Generated_Image_lqpvj0lqpvj0lqpv

Supercharge Your Photo Library: Hosting Immich on Proxmox LXC with TrueNAS & NVIDIA

A technical walkthrough on self-hosting the Immich photo library inside a lightweight, unprivileged Proxmox LXC container. It covers securely mapping a TrueNAS NFS share to bypass unprivileged LXC permission errors, passing through an NVIDIA GPU (GTX 1080ti) to the container, and using Dockge for deployment. The result is a highly secure, hardware-accelerated photo backup system with blazing-fast video transcoding and AI facial recognition.

Gemini_Generated_Image_bta7q3bta7q3bta7

From Wasted Space to Unified Storage

How to repurpose an underutilized bare-metal backup machine into a TrueNAS Scale NAS to create unified, shared storage. To keep backup capabilities without virtualization overhead, Proxmox Backup Server (PBS) is hosted natively on top of TrueNAS inside a lightweight Debian 12 container. The guide explains dataset mapping, bridge networking, and installation steps to create a highly efficient, low-resource backup and storage solution.

In the homelab world, it’s easy to fall into the trap of over-provisioning hardware for a single task. Until recently, I had a dedicated bare-metal machine running Proxmox Backup Server (PBS). It had 2TB of usable storage, but my actual Proxmox VE backups only totaled around 350GB.

Leaving all that unused space locked strictly to backups felt like a massive waste. At the same time, I didn’t have a dedicated NAS appliance on my network. I really needed a centralized place for shared storage—dropping family photos, storing videos, and keeping all my Batocera save files synced up.

The solution? Nuke the bare-metal PBS installation, turn the hardware into a TrueNAS Scale appliance, and run Proxmox Backup Server on top of TrueNAS inside a lightweight Linux container. Here is a detailed look at how I pulled it off.